Rule: The length of the box must be at least eight times (8x) the trade size of the largest raceway (conduit). The NEC provides two distinct methods for sizing junction boxes, depending on wire size: NEC 314. 16 (Box Fill): For smaller conductors (6 AWG and smaller), sizing is based on total volume required. Minimum Length = 8 × Largest Conduit Size Minimum Dimension = 6 × Largest +. Enter wire gauges for box fill or select conduit trade sizes for pull box sizing. What is an Electrical Junction Box Sizing? A junction box sizing calculator is an indispensable tool for electricians and DIY enthusiasts. Pull boxes, junction boxes, and conduit bodies must be sized to allow conductors 4 AWG and larger to be installed without damage to the conductor insulation. Keep in mind these requirements address conductors used for general wiring, such as those. This guide covers the complete NEC sizing rules for pull boxes and junction boxes — when NEC 314. 28, the straight-pull formula, the angle-pull formula, and the U-pull rule — with step-by-step worked examples and a quick-reference sizing chart.